The smart control and I/O system – VIPA SLIO
Presenting the completely new developed I/O system SLIO®, VIPA once again sets new standards in the automation industry.
By means of the modular and extremely compact SLIO the realization of almost every automated solution will from now on be simpler and especially more economical.
SLIO can be combined and applied with each of the established VIPA systems 100V, 200V, 300S, 500S.
It´s one of the most effective and modern decentralized I/O systems available on the market. It combines high functionality with a clever mechanic concept in an extremely compact design.
Features
Compact and Space-Saving Design
- Conceptual separation of electronic and installation layer
- Space-saving, thin design
- Innovative staircase-shaped wiring layer
- Simple “Two components set-up”
Clever Labeling and Diagnostic Concept
- Clear allocation and readability of channel states
- Simple, time-saving installation and maintenance by means of the connector pin assignment provided on the module
- Clear, definite labeling of channels
- Reference designator label remains on the exchange of a module
Installation and Maintainability
- “Permanent Wiring” enables the exchanging without the disconnection of the wiring
- Intelligent slide and plug mechanism for a simple handling
- Electronic is protected against reverse polarity
- Encoding of the electronic modules prevents from incorrect plugging
High performance
- Quick backplane bus concept of 48MBit/s
- With ETS modules it is possible to switch exactly up to +-1us independent of fieldbus.
New: Further safety modules for the approved I/O and control system SLIO available.
SLIO Safety-Modul 021-1SD10 (SDI) and 022-1SD10 (SDO)
The new SLIO Safety-Module with the article number 021-1SD10 and 022-1SD10 is now available. The safety modules support FSoE (FailSafe over EtherCAT) and can be used together with the EtherCAT interface module 053-1EC01 as a slave on an EtherCAT FSoE master.
Properties 021-1SD10
- 4 digital Inputs isolated to the backplane bus, SDI 4xDC 24V
- Status indication of the channels via LEDs
- Safety module with automatic disconnection in case of error according to
IEC 61508 SIL3 and EN ISO 13849-1, Cat.4 / PL e - FSoE (FailSafe over EtherCAT) with EtherCAT Interface-Modul 053-1EC01:
Firmware 2.0.0 and up, ESI file V005 and up
Properties 022-1SD10
- 4 digital outputs isolated to the backplane bus, SDO 4xDC 24V 0.5A
- Status indication of the channels via LEDs
- Safety module with automatic disconnection in case of error according to IEC 61508 SIL3 and EN ISO 13849-1, Cat.4 / PL e
- FSoE (FailSafe over EtherCAT) with EtherCAT Interface-Modul 053-1EC01: Firmware 2.0.0 and up, ESI file V005 and up
Technical data SLIO CPU
013C | 014 | 015N | 015PN | 017PN | |
Load memory [kB] | 128 | 256 | 512 | 512 | 2048 |
Work memory [kB] | 64 – 128 | 128 – 256 | 256 – 512 | 256 – 512 | 512 – 2048 |
Ethernet fieldbus | Modbus TCP / PROFINET | Modbus TCP / PROFINET | Modbus TCP / EtherCAT / PROFINET I-Device | Modbus TCP / PROFINET | Modbus TCP / PROFINET |
Serial fieldbus | PROFIBUS / MPI | PROFIBUS / MPI | PROFIBUS / MPI | PROFIBUS / MPI | PROFIBUS / MPI |
ASCII, STX/ETX, 3964(R), USS master, Modbus master/-slave | yes | yes | yes | yes | yes |
Digital inputs | 16 | – | – | – | – |
Digital outputs | 12 | – | – | – | – |
Counters | 4 | – | – | – | – |
Analog inputs | 2 | – | – | – | – |
RJ45 interface | 2 | 2 | 4 | 4 | 4 |
Max. Number of the expansion modules | 64 | 64 | 64 | 64 | 64 |
Web server | yes | yes | yes | yes | yes |
ENGINEERING TOOL | SPEED7 Studio SIMATIC Manager TIA Portal WinPLC7 | SPEED7 Studio SIMATIC Manager TIA Portal WinPLC7 | SPEED7 Studio SIMATIC Manager TIA Portal | SPEED7 Studio SIMATIC Manager TIA Portal | SPEED7 Studio SIMATIC Manager TIA Portal |